Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SERVICE OUTLET ON ROOF (GFCI) 2) PROVIDE CITY APPROVED ROOF LOAD CALC FOR A/C 3) PROVIDE PROPER COLOR CODE OF LINE VOLTAGE TO A/C 4) PROVIDE CONDUIT ON T-STAT WIRE 5) VERIFY R-8 INSULATION ON ALL ROOF TOP DUCT 6) BLOCK UP CONDENSATE MINIMUM 1.5" ABOVE ROOF 7) CONDENSATE TO TERMINATE 6" ABOVE GRADE 8) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS 9) UNIT DISCONNECT NOT PROPERLY INSTALLED |
|
| 10/20/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE LADDER FOR ROOF ACCESS 2) ITEM 4 ON ELECTRIC RE-CONNECT DATED 10/14/10 LISTED PROVIDING ROOF TOP ACCESS. SINCE YOU HAVE ALREADY BEEN NOTIFIED, THIS PERMIT IS BEING ASSESED WITH A REFEE |