Permit: T10CM02892

Parcel: 13822019B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/08/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
10/19/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE P-TRAP AT CONDENSATE DRAIN
2) PROVIDE SECONDARY DRAIN AT CONDENSATE
3) ALL PVC JOINTS ARE TO BE PRIMERED, PRIMER IS TO BE PURPLE IN COLOR
4) T & P NOT TO BE PIPED UPWARD, PENETRATE FLOOR WITH PIPING. DO NOT USE FLEXIBLE CONNECTIONS