Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/04/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE APPROVED MOUNTING HARDWARE FOR DEVICES 2) ARC SHIELDS TO BE TO THE SURFACE 314.20 3) PANEL MORE THAN 1/4" CAN TO SURFACE 314.20 4) CELAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF PANEL AND BUSHING 110.12 5) NEED ARC FLASH LABELING 110.16 6) NEED PANEL DIRECTORY PER 408.4 7) SUPPORT M/C ABOVE CEILING AS PER CODE 330.30 8) TIGHTEN LOOSE FITTINGS FEEDER RACEWAY |
|
| 02/17/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |