Permit: T10CM02887

Parcel: 119180810


Addresses:

3788 S 16TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM02887

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*DUCT SMOKE SETECTOR TEST OK X2
04/04/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/31/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) AIR BALANCE OK
2) RETURN DUCT NOT SEALED
3) DUCT SMOKE DETECTOR NOT INSTALLED IN LOCATION AS CALLED OUT BY MANUFACTURERS INSTALLATION INSTRUCTIONS