Permit: T10CM02887

Parcel: 119180810


Addresses:

3788 S 16TH AV


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T10CM02887

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
03/01/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection 1. TEST FITTINGS INSTALLED AGAINST FLOW CREATE AN OBSTRUCTION. USE DIRECTIONAL FITTINGS INSTALLED IN THE DIRECTION OF FLOW. 2. INSULATION UNDER SLAB NOT PER PLAN. IF 1/2' WALL ARMAFLEX IS APPROVED BELOW GRADE IT WILL NEED TO BE INSTALLED ACCORDING TO MANUFACTURER'S SPEC'S. 3. HORIZONTAL BY HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP. 4. COPPER UNDERGROUND TO BE TYPE 'K'.