Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T10CM02887
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK |
|
03/01/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | 1. TEST FITTINGS INSTALLED AGAINST FLOW CREATE AN OBSTRUCTION. USE DIRECTIONAL FITTINGS INSTALLED IN THE DIRECTION OF FLOW. 2. INSULATION UNDER SLAB NOT PER PLAN. IF 1/2' WALL ARMAFLEX IS APPROVED BELOW GRADE IT WILL NEED TO BE INSTALLED ACCORDING TO MANUFACTURER'S SPEC'S. 3. HORIZONTAL BY HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP. 4. COPPER UNDERGROUND TO BE TYPE 'K'. |