Permit: T10CM02878

Parcel: 116210720


Addresses:

38 S MELROSE AV

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
05/31/2012 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
06/07/2011 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CICUIT 5/7 PER PLAN 50 AMP BREAKER WITH 6-2 CU WIRE. 30 AMP BREAKER WITH 10-3 WIRE INSTALLED SUBMIT AS BUILT OR INSTALL TO PLAN
2) MISSING CLIPS BEAM TOP RAFTER CONNECTION
3) PROVIDE 1" CLEARANCE B-VENT FROM COMBUSTIBLES
4) GAS FLEX LINE MAY NOT PENETRATE CABINET
5) PROVIDE PROPER LEDGER TO WAL CONNECTION
6) EXPOSE HEADERS FOR WINDOWS 8' WINDOW AND 5' WINDOW
7) SECURE GAS LINE TO CODE