Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2011 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 04/11/2011 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 03/24/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) FIRE WRAP OK |
|
| 03/17/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) GREASE DUCT LEAK/SMOKE TEST OK 2) OK FOR DUCT WRAP |
|
| 03/11/2011 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WELDED GREASE DUCT HAS BEEN CAULKED TO HOOD 2) ALL DUCT WELDS THAT HAVE BEEN CAULKED NEED TO BE GROUND OFF AND RE-WELDED IN ORDER TO ENSURE ALL CAULKING HAS BEEN REMOVED |
|
| 03/10/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST, 1ST LAYER, 2ND LAYER, INSPECTION EACH STAGE 2) NO LIPS,DAMS,TROUGHS AND INSIDE DUCT 3) MVA AND EXHAUST TO BE INTERLOCKED 4) HEAT SENSOR IN HOOD 5) MVA INLET 10' AWAY OR 2' ABOVE ANY VENT 6) PROVIDE HINGE KIT ON EXHAUST FAN 7) THIS IS AN AFTER HOURS INSPECTION, A CHECK #1192 IN THE AMOUNT OF $165.00 HAS BEEN RECEIVED. CHECK IS MADE OUT TO CITY OF TUCSON |
|
| 03/08/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
| 03/07/2011 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 02/23/2011 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 02/15/2011 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* |