Permit: T10CM02877

Parcel: 113090870


Addresses:

2610 N 1ST AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
04/21/2011 MECHANICAL - HOODS Approved IVRS - Inspection :*
04/11/2011 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
03/24/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) FIRE WRAP OK
03/17/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) GREASE DUCT LEAK/SMOKE TEST OK
2) OK FOR DUCT WRAP
03/11/2011 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WELDED GREASE DUCT HAS BEEN CAULKED TO HOOD
2) ALL DUCT WELDS THAT HAVE BEEN CAULKED NEED TO BE GROUND OFF AND RE-WELDED IN ORDER TO ENSURE ALL CAULKING HAS BEEN REMOVED
03/10/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE TEST, 1ST LAYER, 2ND LAYER, INSPECTION EACH STAGE
2) NO LIPS,DAMS,TROUGHS AND INSIDE DUCT
3) MVA AND EXHAUST TO BE INTERLOCKED
4) HEAT SENSOR IN HOOD
5) MVA INLET 10' AWAY OR 2' ABOVE ANY VENT
6) PROVIDE HINGE KIT ON EXHAUST FAN
7) THIS IS AN AFTER HOURS INSPECTION, A CHECK #1192 IN THE AMOUNT OF $165.00 HAS BEEN RECEIVED. CHECK IS MADE OUT TO CITY OF TUCSON
03/08/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
03/07/2011 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
02/23/2011 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
02/15/2011 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*