Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/05/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/29/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4" BOX TO SURFACE OR 1/8" AROUND 314.20 & 21 2) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF PANELS 3) PROTECT CONDUCTORS 300.4 4) NEED ANIT OXID COMPOUND ON ALUMINUM CONDUCTORS 5) LABEL DIRECTORY PER 408.4 6) ALL KITCHEN RECEPTS TO BE GFCI PROTECTED 210.8 (B) 7) CLEAN SURFACE GROUND BAR 250.12 8) NEED LISTED REPORT RELAYS NOT RECOMMENDED COMPONENTS 9) REPLACED BALLAST TO BE PER 410.73 (G) |