Permit: T10CM02877

Parcel: 113090870


Addresses:

2610 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/12/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/05/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/29/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOXES MORE THAN 1/4" BOX TO SURFACE OR 1/8" AROUND 314.20 & 21
2) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF PANELS
3) PROTECT CONDUCTORS 300.4
4) NEED ANIT OXID COMPOUND ON ALUMINUM CONDUCTORS
5) LABEL DIRECTORY PER 408.4
6) ALL KITCHEN RECEPTS TO BE GFCI PROTECTED 210.8 (B)
7) CLEAN SURFACE GROUND BAR 250.12
8) NEED LISTED REPORT RELAYS NOT RECOMMENDED COMPONENTS
9) REPLACED BALLAST TO BE PER 410.73 (G)