Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/09/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/03/2010 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled | |
| 11/03/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) WILL NEED ANOTHER INSPECTION AND CLEARANCE IF TEP DOES NOT ACCEPT SERVICE PANEL BOARD 2) OK GROUND RODS 3) OK WATER BOND 4) VERIFY GAS PIPING IS BONDED OR BOND GAS PIPING TO SERVICE PANEL 5) PROVIDE INFORMATION ON PANEL BOARD THAT BUSSING IS RATED FOR 225A. HAVE THIS INFORMATION AT INSPECTION FOR PV SYSTEM |