| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/08/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CONTRACTOR |
|
| 12/01/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) 1/2" I.D. X 18" GAS FLEX NOT ADEQUATE FOR 180,000 BTU 2) PROVIDE CHASE NIPPLES IN DISCONNECTS AS NEEDED 3) SUPPORT PVC DRAIN LINES AND REPAIR BROKEN FITTINGS 4) PROVIDE A SEDIMENT TRAP AT A/C 5 5) PAINT EXPOSED PVC BETTER WITH LATEX PAINT 6) A/C 5 REQUIRES A DUCT SMOKE DETECTOR WITH AUDIBLE AND VISIBLE ALARM |