Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T10CM02836
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) THERE MAY BE NO FOULING LEDGE IN THE CLOSET BEND |
|
11/07/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CLOSET FLANGE IS TO EXTEND 1/4" ABOVE FINISHED FLOOR -EXPOSE ALL FLANGES |
|
11/04/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 100 PSI ON BLACK STEEL AIR PIPING, NO PLANS SPECS PROVIDED 2) INSTALL QD FOR DETAIL |
|
11/04/2011 | PLUMBING - INTERMEDIATE | Approved | ||
07/08/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DWV CORRECTIONS OK 2) LAV CARRIERS SPECIFIED 3) CLOSET FLANGES NOT SECURED TO F.F. |
|
07/07/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) TRAP WEIR MAY NOT BE BELOW THE POINT OF VENT REPIPE DBL SINK |
|
07/01/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TRAP AND TRAP ARM TO BE THE SAME SIZE TRAP MAY BE ONLY ONE SIZE LARGER THEN CONNECTING TAIL PIECE-TRAP ARM MAY NOT CHANGE SIZE. TRAP ARM TO CONNECT THRU SANTEE 2) VENT FITTINGS LESS THAN 6" ABOVE FLOOD RIM TO BE DRAINAGE TYPE 3) VENT CONNECTS DOWN STREAM OF TRAP 4) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE SWEEP |
|
06/16/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PLUMBER NOT ON SITE 2) CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE |
|
06/13/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) DELTA 2 REVISION DELETES GREASE TRAP 2) PLUMBING IS STILL NOT INSTALLED PER PLAN 3) HAVE PLUMBER ON SITE AT TIME OF NEXT INSPECTION 4) AS CORRECTIONS ARE TO NUMEROUS AND COMPLICATED TO LIST 5) CLEANOUTS TO OPEN IN THE DIRECTION OF FLOW 6) SEWER ON NORTH SIDE OK TO COVER |