Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T10CM02836
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2011 | ELECTRIC - PROGRESS | Approved | ||
09/01/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
08/31/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) WALL OUTLETS GFI'S OK 2) PANELS A, B AND C OK |
|
07/15/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
07/11/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK U.G. UNDER SIDEWALK ONLY 2) ROAD OR DRIVE WAY CROSSING 24" OTHER 18" PER 300.4 NEC |
|
06/16/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) WALLS IN BLDG OK AND PUT IN FILE |
|
06/13/2011 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) M/C TO BE 1 1/4 FROM EDGE 2) M/C NOT TO BE USED BY PRINT 3) PVC 40 0R 80 NOT TO BE USED ABOVE GRADE 4) M/C MISSING BOXES |