Permit: T10CM02836

Parcel: 12901018M


Addresses:

191 S PLUMER AV

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
11/04/2011 ELECTRIC - PROGRESS Approved
09/01/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/31/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) WALL OUTLETS GFI'S OK
2) PANELS A, B AND C OK
07/15/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/11/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK U.G. UNDER SIDEWALK ONLY
2) ROAD OR DRIVE WAY CROSSING 24" OTHER 18" PER 300.4 NEC
06/16/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) WALLS IN BLDG OK AND PUT IN FILE
06/13/2011 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) M/C TO BE 1 1/4 FROM EDGE
2) M/C NOT TO BE USED BY PRINT
3) PVC 40 0R 80 NOT TO BE USED ABOVE GRADE
4) M/C MISSING BOXES