Permit: T10CM02835

Parcel: 10511061E


Addresses:

150 W WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM02835

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/20/2011 ELECTRIC - INTERMEDIATE Approved
06/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MAINTAIN WORKING CLEARANCES AT DISCONNECTS 110.26
2) MAINTAIN WORKING CLEARANCES AT DISCONNECTING MEANS 110.26
3) OK RTU-1,2,3 & 5 TO ENERGIZE, OK MDP,SDP,LPA,LPB,LPC,LPD AND LPL TO MAINS AND OK EEF1,23
05/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED LETTER OF TORQUE
2) SECURE SWITCH BOARD TO FLOOR
3) CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT
4) OK TO CLEAR TMPP SUBJECT TO BOND
05/05/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK TOWER ON ROOF
05/03/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK WEST END OF CENTER WALLS ROOMS 104, 105
04/29/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/27/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NO MORE THAN 360 DEGREES IN CONDUIT RUNS - EAST SIDE FIRE ALARM
2) USE ADEQUATE STRENGTH SCREWS FOR BOXES
04/26/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/25/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/18/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK KITCHEN RESTROOM, FEEDER THRU WALK IN COOLER, STORAGE, FRONT ENTRY LTG ROUGH AND RECEPTS
04/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/30/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/25/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK LIGHTS AT OUTSIDE UP HIGH
2) NEED GROUNDED CONDUCTOR AT SERVICE 250.24 (C)
3) NEED GROUNDING ELECTRODE SYSTEM AT SERVICE
4) SECURE BACKFED BREAKER WITH MANUFACTURERS HOLDOWN 408.16
5) FITTING TO BE FOR WET LOCATION
03/24/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) OK LAST PVC TO CONCENTRICS 4" FEEDERS