Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM02835
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2011 | ELECTRIC - INTERMEDIATE | Approved | ||
06/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCES AT DISCONNECTS 110.26 2) MAINTAIN WORKING CLEARANCES AT DISCONNECTING MEANS 110.26 3) OK RTU-1,2,3 & 5 TO ENERGIZE, OK MDP,SDP,LPA,LPB,LPC,LPD AND LPL TO MAINS AND OK EEF1,23 |
|
05/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED LETTER OF TORQUE 2) SECURE SWITCH BOARD TO FLOOR 3) CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT 4) OK TO CLEAR TMPP SUBJECT TO BOND |
|
05/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TOWER ON ROOF | |
05/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WEST END OF CENTER WALLS ROOMS 104, 105 | |
04/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 360 DEGREES IN CONDUIT RUNS - EAST SIDE FIRE ALARM 2) USE ADEQUATE STRENGTH SCREWS FOR BOXES |
|
04/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK KITCHEN RESTROOM, FEEDER THRU WALK IN COOLER, STORAGE, FRONT ENTRY LTG ROUGH AND RECEPTS |
|
04/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK LIGHTS AT OUTSIDE UP HIGH 2) NEED GROUNDED CONDUCTOR AT SERVICE 250.24 (C) 3) NEED GROUNDING ELECTRODE SYSTEM AT SERVICE 4) SECURE BACKFED BREAKER WITH MANUFACTURERS HOLDOWN 408.16 5) FITTING TO BE FOR WET LOCATION |
|
03/24/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) OK LAST PVC TO CONCENTRICS 4" FEEDERS |