Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM02828
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
11/30/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM 2 & 6 NOT CORRECTED |
|
10/15/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A PROTECTIVE COATING ON ALL EXPOSED INSUTLATION IN LINE SET 2. RELOCATE DISCONNECT LOCATED BEHIND WEST A/C UNIT. THIS DISCONNECT DOES NOT HAVE PROPER ACCESS + CANNOT IDENTIFY PROPER FUSING 3. EAST A/C IS OVERFUSED 4. MARK FAN COIL DATA PLATES W / PROPER HEAT STRIPS + FUSE ACCORDINGLY 5. I.D. CIRCUIT BREAKERS. IF NO HEAT STRIP, BREAKER SHOULD BE 15 AMP. BREAKER IN FAN COIL IS 30 AMP. 6. PERMANENTLY I.D. FAN COILS + A/C UNITS. |