Permit: T10CM02828

Parcel: 141011370

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM02828

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
11/30/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM 2 & 6 NOT CORRECTED
10/15/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE A PROTECTIVE COATING ON ALL EXPOSED INSUTLATION IN LINE SET
2. RELOCATE DISCONNECT LOCATED BEHIND WEST A/C UNIT. THIS DISCONNECT DOES NOT HAVE PROPER ACCESS + CANNOT IDENTIFY PROPER FUSING
3. EAST A/C IS OVERFUSED
4. MARK FAN COIL DATA PLATES W / PROPER HEAT STRIPS + FUSE ACCORDINGLY
5. I.D. CIRCUIT BREAKERS. IF NO HEAT STRIP, BREAKER SHOULD BE 15 AMP. BREAKER IN FAN COIL IS 30 AMP.
6. PERMANENTLY I.D. FAN COILS + A/C UNITS.