Permit: T10CM02814

Parcel: 11006017A

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/17/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/03/2010 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORRECT LEAK ON SINK DRAIN, ADD CLEANOUT AT SINK
2) VENT TAKE OFF SHALL BE ABOVE CENTER LINE OF PIPE (INSTALL AT A 45 DEGREE)
3) SUPPORT 3" ABS BELOW FLOOR
4) SAFETY PLATES MISSING
5) RECIRC HOT WATER REQUIRES INSULATION
10/21/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE A TEST ON PIPING
2) INSTALL SAFETY PLATES
3) SECURE ALL TUBING
4) PROVIDE CORRECT TRANSITION AT 3" ABS TO 4" ?
5) PROVIDE HARD CAPS ON LIVE DEMO
6) PROVIDE FULL SIZED 3" CLEANOUT