Inspection History: ELECTRIC - FINAL

Permit Number - T10CM02806

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING OF PV PANELS AT RACKING SYSTRM TO BE PER MANUFACTURERS INSTRUCTIONS. USE PROPER WEEB LUG WITH WASHER. INSTALL GROUND CLIPS BETWEEN PANELS PER INSTRUCTIONS
2) CANNOT RUN OPEN CONDUCTORS UNDER ROOFM TILES TO PV ARRAY. INSTALL IN 3/4" CONDUIT PER PLANS
3) CANNOT USE TEK SCREWS FOR CONNECTION OF GROUNDS USE MACHINE SCREW OR NUT AND BOLT
4) INSTALL LABELING PER NEC 690