Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM02806
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/05/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING OF PV PANELS AT RACKING SYSTRM TO BE PER MANUFACTURERS INSTRUCTIONS. USE PROPER WEEB LUG WITH WASHER. INSTALL GROUND CLIPS BETWEEN PANELS PER INSTRUCTIONS 2) CANNOT RUN OPEN CONDUCTORS UNDER ROOFM TILES TO PV ARRAY. INSTALL IN 3/4" CONDUIT PER PLANS 3) CANNOT USE TEK SCREWS FOR CONNECTION OF GROUNDS USE MACHINE SCREW OR NUT AND BOLT 4) INSTALL LABELING PER NEC 690 |