Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/22/2010 | PLUMBING - INTERMEDIATE | Denied | 1) SECURE AND SUPPORT PIPING AT STORAGE TANK 2) PROVIDE ACCESS TO CONTROL PANEL 3) SHINNERS PRESENT AT SAFETY HAZARD 4) SEAL PIPING AT ENCLOSURE PENETRATIONS 5) PUT IN THE REST OF THE HINGE SCREWS 6) COAT/PROTECT 10 MILL TAPE AND INSULATION ON ROOF 7) PROVIDE SAFE ACCESS TO INSPECTION ROOF 8) CONNECT T & P TO EXISTING DRAIN, UNLESS THE DRAIN IS PLUGGED-THEN PROVIDE AN APPEAL FORM 9) REMOVE INSULATION WITHIN 6" OF VENT 10) CORRECT GAS LEAK ON FURNACE SUPPLY, CHECK WITH SOAP |