Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM02795
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
06/03/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WHERE ARE OCCUPANCY SENSORS ? 2) CANNOT USE SHEET METAL SCREWS FOR GROUNDING 250.8 3) BOXES MORE THAN 1/4" 314.20 OR 1/8" 314.21 4) VDV CABLING LAYING AND HANGING OUT OF CEILING BACK DOOR 725.8 AND 300.11 5) FINISH LABELING LIGHTING PANEL 408.4 |
|
05/31/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* BUILDING LOCKED NO PERSON ON SITE TRIED TO CALL NO ANSWER RE-SCHEDULE INSPECTION |