Permit: T10CM02795

Parcel: 11619359A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM02795

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/07/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
06/03/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) WHERE ARE OCCUPANCY SENSORS ?
2) CANNOT USE SHEET METAL SCREWS FOR GROUNDING 250.8
3) BOXES MORE THAN 1/4" 314.20 OR 1/8" 314.21
4) VDV CABLING LAYING AND HANGING OUT OF CEILING BACK DOOR 725.8 AND 300.11
5) FINISH LABELING LIGHTING PANEL 408.4
05/31/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED NO PERSON ON SITE
TRIED TO CALL NO ANSWER
RE-SCHEDULE INSPECTION