Permit: T10CM02789

Parcel: 119220130


Addresses:

2002 W MERLIN RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/26/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/24/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
1. FRONT WINDOW HEADER SIZE 2X4 TOO SMALL FOR 5' 5" WINDOW. INSTALL DOUBLE 2X6" HEADERS
2. PROVIDE APPROVED CEILING FAN BOXES
3. ALL JUNCTION BOXES IN ATTIC MUST BE ACCESSIBLE
4. PER OWNER NO CAN LIGHTS TO BE INSTALLED PER PLAN
5. BLOCK REGISTER BOLTS 3 SIDES
6. SECURE ROMEX 8" FROM BOLTS
7. RMOVE INSULATION FOR INSPECTION