Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/25/2011 | BUILDING - FINAL | Denied | 1) FURNACE ALTERED OR MODIFIED WITHOUT PERMITS a) PROVIDE WORKING CLEARANCE FRONT OF FURNACE b) PROPERLY SECURE ELECTRICAL CONDUITS 2) PLUMBING REQUIRES REPAIR a)SECURE TOILET TO FLOOR AND CAULK AT FLOOR b) DRAINAGE FITTINGS UNDER LAVATORY ARE NOT LISTED AND NOT INSTALLED PER CODE. HAVE LICENSED PLUMBER MAKE REPAIRS. c) CAULK LAVATORY AT WALL 5) ELECTRICAL INSTALLED WITHOUT INSPECTIONS a)OPEN WALLS AS NOTED FOR PARTIAL ELECTRIAL OBSERVATION. (ONE SWITCH, TWO OUTLETS AS NOTED) b) OPEN OUTLETS ON WEST WALL AS DISCUSSED c) PROPER BUSHINGS REQUIRED WHERE NEW WIRING PULLED INTO SUB-PANEL d) MAKE SURE PANEL LABELS ARE CORRECT e) REMOVE 1 LIGHT FOR OBSERVATION OF INSTALLATION 4) FRAMING DONE WITHOUT INSPECTION BUT APPEARS SOLID a) FLOOR OF RESTROOM MUST EXTEND 6" UP SIDE OF WALLS b) REPAIR PLUMBING WALL UNDER LAVATORY |