Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM02741
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/05/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PROPER WORKING CLEARANCES IN FRONT OF EQUIPMENT. NEC 110.26 2) PROVIDE WARNING LABELS ON SERVICE PANEL PER PLANS-SEE NOTES 8 & 11 3) INSTALL GEC TO MIRCO INVERTERS TO BE SIZED PER NEC 250.66 AND 690.47 SEE NOTE #6 ON PLANS |