Permit: T10CM02741

Parcel: 136175670


Addresses:

8418 E DOMENIC DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM02741

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/05/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PROPER WORKING CLEARANCES IN FRONT OF EQUIPMENT. NEC 110.26
2) PROVIDE WARNING LABELS ON SERVICE PANEL PER PLANS-SEE NOTES 8 & 11
3) INSTALL GEC TO MIRCO INVERTERS TO BE SIZED PER NEC 250.66 AND 690.47 SEE NOTE #6 ON PLANS