Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10CM02721

Parcel: 13332013J


Addresses:

9485 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/26/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/22/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) AIR BALANCE REPORT OK
2) LINE SETS ON ROOF TO BE COATED FOR U.V. PROTECTION, NO DUCT TAPE
3) PLUG CLEANOUT TEE'S ON ROOF
4) UNIT DATA PLATES NOT IDENTIFIED
5) UNITS NOT LABELED
6) DUCT SMOKE DETECTOR TEST OK