Permit: T10CM02721

Parcel: 13332013J


Addresses:

9485 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/02/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
08/01/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) IMPROPER CONNECTION TO MOP SINK FAUCET, ABOVE MAY NOT HAVE VALVES DOWN STREAM
2) FO SYSTEM LEAKING, PROVIDE RIGID PIPING AT DRAIN TERMINATIONS
3) SUPPORT BACKFLOW ASSEMBLIES
4) LETTERS RECEIVED FOR CHANGES PER ERIC
07/28/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE STERILIZATION DOCUMENTED PROCEDURES AND TEST REPORT
2) PROVIDE RP CERT FOR IRR ASSEMBLY
3) SVB REQUIRES CERT BUT IT ALSO MAY NOT BE INSTALLED MORE THAN 5' ABOVE PLATFORM
4) BACKFLOW ASSEMBLIES REQUIRE UNIONS FOR SERVICING
5) COMPLETE RO SYSTEM, TRAP PRIMERS WITH AIR CAP FIITINGS SPECIFIED, ECO LAB INSTALLATION AND DOME STRAINERS