Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/27/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND JUMPERS ON SUPPLY SIDE 250.66, 250, 102 C 2) 1000 A 480 V MAIN BRKR TO BE GFI PROTECTED PER 230.95 NEC 3) CONDUCTOR SIZES TO MATCH PLAN 4) OK DPN #1 AND X-FORMER AND PANEL |