Permit: T10CM02681

Parcel: 117032880

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM02681

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
09/29/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) T-STAT WIRE OUTDOORS IS TO BE PROTECTED
2) UNITS ARE OVER FUSED PROVIDE 20 AMP X 4
3) CONDENSATE NOT PROPERLY TERMINATED