Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM02664
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
10/06/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX. SUPPORT REFRIDGERATION LINE ON ROOF 2) FAN COIL IS SMALLER THAN THE DUCT CONNECTION. DO NOT USE TAPE TO BLANK OFF OPENING. USE SHEET METAL, THEN SEAL AROUND CONNECTION 3) OVERFLOW SENSOR TO BE CONNECTED TO FAN. COIL, NOT PRIMARY DRAIN. EXTEND VENT ABOVE DRAIN PAN 4) MAKR UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED |