Permit: T10CM02664

Parcel: 141011360

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM02664

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/06/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX. SUPPORT REFRIDGERATION LINE ON ROOF
2) FAN COIL IS SMALLER THAN THE DUCT CONNECTION. DO NOT USE TAPE TO BLANK OFF OPENING. USE SHEET METAL, THEN SEAL AROUND CONNECTION
3) OVERFLOW SENSOR TO BE CONNECTED TO FAN. COIL, NOT PRIMARY DRAIN. EXTEND VENT ABOVE DRAIN PAN
4) MAKR UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED