Inspection Status: Partial Approval
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 |
|
| 11/30/2010 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAIN IS NEEDED AT SUB PANELS 225.31 & 32 2) SUPPORT PVC RISERS TO SUB PANELS 3) LABEL EQUIPMENT AND PANELS 4) PROTECT CONDUCTORS 352.46 & 300.4 5) SECURE SES TO PAD 6) PVC ENTERING SES NOT HIGHER THAN 3" 408 |