Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/23/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WORK HAS NOT BEEN DONE, A REFEE IS BEING ASSESED TO THIS PERMIT |
|
| 12/20/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL ROOF PENTRATIONS ARE TO HAVE ROOF JACK ( SERVICE OUTLET) 2. ITEM 4 DATED 12-210 STILL NOT CORRECTED 3. ARE-FEE WILL BE ATTACHED TO THIS ACTIVITY IF ALL ITEMS ARE NOT CORRCTED PRIOR TO NEXT INSPECTION |
|
| 12/02/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONDENSATE TO TERMINATE AT AN APPROVED LOCATION. CANNOT TERMINATE AT WAST VENT. REMOVE MASTIC FROM BLOCKING WASTE VENT 2) PROVIDE SUPPORT UNDER GAS PIPING 3) ALL PVC JOINTS ARE TO BE PRIMERED, ALL PRIMER IS TO BE PURPLE IN COLOR PER U.P.C. 4) ALL PVC EXPOSED TO DAYLIGHT IS TO BE COATED FOR U.V. PROTECTION 5) PROVIDE SERVICE OUTLET WITHIN 25' OF UNIT, DO NOT POWER WITH LINE VOLTAGE FROM UNIT. OUTLET IS TO BE GFI PROTECTED WITH BUBBLE COVER 6) UNIT DISCONNECT NOT PROPERLY INSTALLED, RAISE UP OFF OF ROOF MIN. 1.5" TO AVOID WATER MIGRATION. ACCESS TO DISCONNNECT BLOCKED BY GAS PIPE AND CONDENSATE PIPING |