Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2014 | FIRE - FINAL | Approved | ||
| 11/03/2014 | FIRE - FINAL | Denied | 1. All labels to service disconnect shall be replaced they are damage and very hard to read 2. Security gates (access gates on to property) shall open when power fails and stay open until power is restored. When testing power failure by shut the breaker off gates failed to open. Also needs a manual override install on the entrance side incase batteries fail or were removed when gates are closed. 3. Need 12" address number posted on front and sizes of building, handout given. |