Permit: T10CM02649

Parcel: 14017001A


Addresses:

1514 E IRVINGTON RD

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
02/12/2015 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/31/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/24/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNIT 43-OK AND 6-OK
10/13/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL DOWN STAIRS UNITS EXCLUDING 3, 6, 43 DUCT ABOVE CEILING OK TO COVER
10/12/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DUCT ABOVE SOFFITS UNITS #40,41,14,11,10,9,7,6 AND 4 OK TO COVER
10/04/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNITS 31, THRU 40 - DUCT TO LIVING AREA IS COMPRESSED, EXPAND DUCT PRIOR TO SHEET ROCK NO OTHER UNITS LOCKED AT
09/26/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/09/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROVIDE SECONDARY DRAIN (G2 TRAP)
2) INSULATE LINE SET OVER DRAIN PAN
3) PROVIDE PROTECTIVE GRUMMET OR SLEEVE AT CABINET PENETRATIONS
4) PROVIDE VENT DOWN STREAM OF TRAP OUT SIDE OF CABINET
5) REPAIR ALL TARES IN LINE SET INSULATION
6) CANS ARE TO BE FRAMED ON 3 SIDES