Permit: T10CM02649

Parcel: 14017001A


Addresses:

1514 E IRVINGTON RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/12/2015 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/20/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNITS #30-#35 CLOSET FLANGES OK
12/29/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/05/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SEE NOTES FROM 09/08/11
09/08/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) HAVE ALL CLOSET FLANGES READY FOR INSPECTION
2) CLOSET FLANGES AND TO EXTEND 1/4" ABOVE FINISHED FLOOR
3) FLANGES ARE TO9 BE SECURED
4) 2ND FLOOR FLANGES TO BE SECURED WITH S.S. OR BRASS SCREWS
09/07/2011 PLUMBING - INTERMEDIATE Cancelled IVRS - RI canceled
09/07/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CONDENSATE PIPING IS INSPECTED BY MECHANICAL INTERCEPTOR
2) CALL IN ITEM 04035
08/10/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED TO SEE CLOSET FLANGES
2) WALLS OK
3) CONDENSATE UNIT #1 OK-CALL 04035 (MECH) FOR CONDENSATE
06/16/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WHILE BUNDLING OF PEX IS PERMITTED, ISOLATE HOT FROM COLD TO HELP PRVENT HEAT TRANSFER
2) CPVC T & P RELIEF DRAINS 6"-24 AFF
3) TUBS OK
05/26/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED COUPLINGS ON TUB DRAINAGE AND PROVIDE TEST ON NEW TUBS
2) PEX TO BE INSTALLED WITH CORRECT RADIUS ON TUBING OR PROVIDE FITTINGS FOR CHANGE OF DIRECTION
3) PROVIDE 18" IN WALL COPPER PER NOTED 1/26/11 INSPECTION
4) PROVIDE TEST ON ALL WATER PIPING
5) SEAL TUB BOXES ON EXISTING TUBS
05/24/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ACCESS TO SITE, HAVE YOUR PLUMBER ON SITE FOR NEXT INSPECTION
01/26/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROVIDE 18" OF COOPER BEFORE TIEING INTO PEX AT WATER HEATER PER 2006 UPC 604.11.2
10/15/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
COVER ALL OPEN ABS PIPING IN UNITS AND CLOSET FL?/?

UNITS #48 + #49 + #33 IN WALL WATER PIPING OK
10/14/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/13/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WALK THRU WITH PLUMBING