Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/12/2015 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/27/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/23/2013 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/23/2013 ELECTRIC - INTERMEDIATE Denied - GROUNDING SYSTEM GONE AT 23, 24
- VERIFY WATER & GAS PIPE BONDING INTACT FOR ALL OTHER UNITS
- INSTALL PERMANENT, LEDGIBLE ADDRESS OR UNIT #'S ON SERVICE EQUIP
- MESSAGE LEFT WAS FOR POWER CLEARANCE #23-#30
- MIXED BRANDS OF CIRCUIT BREAKERS IN SUB-PANELS
12/13/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #43,44,45,46, DID NOT GET INSPECTED-WALLS COVERED PRIOR TO INSPECTION, REMOVE DRYWALL AND RECALL INSPECTION FOR INTERMEDIATE
09/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WHY IS SERVICE FOR LAUNDRY/OFFICE NOT GROUNDED
2) VERIFY AIR RATING WITH TEP
3) NO EXPOSED WIRING IN AIR HANDLER
4) UNITS #31 THRU 40 OK WALLS
5) BOND WATER LINE (MISSING) AT UNIT #39
6) CONTRACTOR TO LOCK OUT/TAG OUT
08/04/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SERVICE SECTION FOR HOUSE/AND OR LAUNDRY PANEL NEED TO BE REPLACED, THERE IS EXTENSIVE OXIDATION & RUST TO WEATHER EXPOSURE
- USE REMEX CONNECTORS INSTALLED PER LISTING AT PANEL INSIDE. INSPECTION AT BLD #1
06/20/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS/PERMIT ?
2) CONTRACTOR ON SITE, PLEASE OPEN EQUIPMENT
01/26/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK #31,33,35,37,38,39,41,42 STILL NEED TO SOLVE A/C ISSUES
11/03/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) REPLACE BROKEN BOX #48
2) USE APPROVED SPLICE CONNECTORS ON GROUNDS
3) WHAT IS BEING DOINE FOR HEATING/COOLING OF UNITS ?
4) OK 47-60 WALLS
10/20/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) W/P BOXES
2) CONTRACTOR TO REQUEST CLARIFICATION FOR NOTES AND #4 & 5 FROM BLDG OFFICIAL
10/15/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
* 314.20 WILL APPLY ALSO 314.21

1. FILL UNUSED APENING IN BOXES
2. GROUND SWITCHES
3. STRAP NM WITH IN 12"
4. DISCONNECT TO BE WITH WATER HEATER NOT IN UPPER CABINET
5. VERIFY KITCHEN COUNTER CIRCUIT 210.52
6. BOX OVER FILLED
7. PROTECT NM CABLE