Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 09/27/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TURN DISCONNECT 90 DEGREE TO ALLOW PROPER ACCESS. PROPERLY INSTALL COVER PLATE IN DISCONNECT 2) PERMANENTLY I.D. HEAT STRIP ON UNIT DATA PLATE AND FUSE ACCORDINGLY. NO INK 3) TERMINATE CONDENSATE TO AN APPROVED LOCATION 4) ID FUSE BANKS ON COVER PLATE FOR DISCONNECT 5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF |