Permit: T10CM02645

Parcel: 133152660

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/08/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/27/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TURN DISCONNECT 90 DEGREE TO ALLOW PROPER ACCESS. PROPERLY INSTALL COVER PLATE IN DISCONNECT
2) PERMANENTLY I.D. HEAT STRIP ON UNIT DATA PLATE AND FUSE ACCORDINGLY. NO INK
3) TERMINATE CONDENSATE TO AN APPROVED LOCATION
4) ID FUSE BANKS ON COVER PLATE FOR DISCONNECT
5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF