Permit: T10CM02631

Parcel: 14027048A


Addresses:

2850 E GANLEY RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/16/2011 ELECTRIC - FINAL Approved
12/07/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOND BUSHING AT CONCENTRIC 250V OR GREATER 250.97
2) AIR COMPRESSOR AND DUST COLLECTOR NEED 3RD PARTY OR NRTL EVALUATION
11/03/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROTECT CONDUCTOR AT FITTINGS #4 AND LARGER 300.4
2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 120/240
3) BOND RACEWAYS FOR TRANSFORMER
4) DO NOT STCK LUGS AND DO NOT INSTALL ON TOP OF ISOLATION STRAP
5) GROUND DEVICE JUNCTION BOXES
6) SUPPORT EMT WITHIN 3' OF BOXES
7) PLANS CALL FOR DISCONNECTING MEANS AT EQUIPMENT
8) WHERE IS OUTSIDE GFI ?
9) LABEL PANELS AS MARKED ON PLAS
10) ALL EQUIPMENT SHALL BE LISTED AND LABELED AS STAMPED ON PLANS-PLEASE VERIFY
10/14/2010 ELECTRIC - FINAL Cancelled IVRS - RI canceled
10/06/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/05/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED GROUNDED CONDUCTOR TO SERVICE DISCONNECT 250.24 (C)
2) BOND JUMPER TO BE SIZED PER 250.66
3) NEED "R" CLIPS