Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2011 | ELECTRIC - FINAL | Approved | ||
| 12/07/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND BUSHING AT CONCENTRIC 250V OR GREATER 250.97 2) AIR COMPRESSOR AND DUST COLLECTOR NEED 3RD PARTY OR NRTL EVALUATION |
|
| 11/03/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROTECT CONDUCTOR AT FITTINGS #4 AND LARGER 300.4 2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 120/240 3) BOND RACEWAYS FOR TRANSFORMER 4) DO NOT STCK LUGS AND DO NOT INSTALL ON TOP OF ISOLATION STRAP 5) GROUND DEVICE JUNCTION BOXES 6) SUPPORT EMT WITHIN 3' OF BOXES 7) PLANS CALL FOR DISCONNECTING MEANS AT EQUIPMENT 8) WHERE IS OUTSIDE GFI ? 9) LABEL PANELS AS MARKED ON PLAS 10) ALL EQUIPMENT SHALL BE LISTED AND LABELED AS STAMPED ON PLANS-PLEASE VERIFY |
|
| 10/14/2010 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 10/06/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/05/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED GROUNDED CONDUCTOR TO SERVICE DISCONNECT 250.24 (C) 2) BOND JUMPER TO BE SIZED PER 250.66 3) NEED "R" CLIPS |