Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/22/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) NEED PANEL DIRECTORY 2) PROVIDE FUSES IN ELECTRIC DISCONNECT 3) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF 4) DO NOT USE WHITE WIRE FOR POWER TO A/C UNIT. TAPE BOTH ENDS WITH BLACK TAPE 5) COMPLETELY COVER ALL PORTIONS OF CANVAS CONNECTORS FROM SUN DAMAGE 6) COMPLETELY SEAL AROUND SUPPLY AND RETURN ELBOWS ON ROOF 7) OUTDOOR RECEPTS TO BE GFI PROTECTED AND HAVE WEATHER PROOF COVERS 8) THIS IS A PARTIAL APPROVAL ON SERVICE UPGRADE PENDING TEP APPROVAL LOCATION OF SERVICE CONDUCTORS OVER POOL. WILL NEED NEW CLEARANCE IF SERVICE IS TO BE MOVED |