Permit: T10CM02607

Parcel: 11618075B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/09/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/01/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOND BUSHING ON OFF SET NIPPLE NOT BONDED BETWEEN METER BASE AND PANEL
2) EXPOSE GROUND RODS, GAS, WATER BONDING
3) BACK FED MAIN BREAKER MUST HAVE HOLDDOWN HARDWIRE
4) INSTALL PERMANENT ADDRESS LABEL
5) ISOLATE GROUNDS AND NEUTRALS