Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/01/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND BUSHING ON OFF SET NIPPLE NOT BONDED BETWEEN METER BASE AND PANEL 2) EXPOSE GROUND RODS, GAS, WATER BONDING 3) BACK FED MAIN BREAKER MUST HAVE HOLDDOWN HARDWIRE 4) INSTALL PERMANENT ADDRESS LABEL 5) ISOLATE GROUNDS AND NEUTRALS |