Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/04/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4" 314.20 2) ARC FLASH LABELING NEEDED 110.16 3) PROTECT CONDUCTORS AT FITTINGS 300.4 4) PROPERLY IDENTIFY FEEDER CONDUCTOR 210.5 (C) AMENDMENTS 5) FEEDER CONDUCTORS NOT PER PLANS, ALSO RACEWAY 6) CIRCUIT DIRECTORY TO BE PER 408.4 |
|
| 03/02/2011 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |