Permit: T10CM02601

Parcel: 12810079C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM02601

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/08/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/04/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOXES MORE THAN 1/4" 314.20
2) ARC FLASH LABELING NEEDED 110.16
3) PROTECT CONDUCTORS AT FITTINGS 300.4
4) PROPERLY IDENTIFY FEEDER CONDUCTOR 210.5 (C) AMENDMENTS
5) FEEDER CONDUCTORS NOT PER PLANS, ALSO RACEWAY
6) CIRCUIT DIRECTORY TO BE PER 408.4
03/02/2011 ELECTRIC - FINAL Cancelled IVRS - RI canceled