Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T10CM02590
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
03/25/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) WASTE PIPE OK INSTALL ABOVE SLAB 2) TEST FITTINGS AND RETEST AT PRE-SLAB INSPECTION |
|
03/23/2011 | PLUMBING - ROUGH, SOIL | Denied | 1. PROVIDE WYE PATTERN TEST FITTING. PROVIDE SHIELDED COUPLINGS INSIDE THE BUILDING. PROVIDE MINIMUM REQUIRED SLOPE. PROPER VENTING. WEIR OF TRAP MAY NOT BE ABOVE VENT AKE OFF. VENT TAKE OFF SHALL BE ABOVE CENTER LINE OF PIPE. | |
03/22/2011 | PLUMBING - ROUGH, SOIL | Cancelled | IVRS - RI canceled |