Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T10CM02583
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2011 | FRAMING | Approved | IVRS - Inspection :* | |
05/16/2011 | FRAMING | Partial Approval | IVRS - Inspection :* 1) SEE LAST INSP. SHEET |
|
05/13/2011 | FRAMING | Partial Approval | IVRS - Inspection :* 1)FIREBLOCKING 2)DRYER DUCT - MOVE & TAPE 3)TRUSS BEARING 4)DWV 5)R-8 DUCTS & MASTIC 6)BLOCK DUCT BOOTS | |
05/10/2011 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL OPEN KNOCKOUT IN PANEL 2) J-J CHANNEL IS WRONG SWEEP SCREED FOR MESH 3) PEX CANNOT BE WITHIN 12" OF A CAN LIGHT 4) ALL FURRED WALLS MUST BE FIRE BLOCKED 5) WASHER BOX IS TO LOW 6) STOPPED INSPECTION 7) RECALL INSPECTIONS AND LEAVE MESSAGE WITH CONTRACTOR NUMBER FOR MEET AT SITE |