Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/04/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #8 WIRE ONLY GOOD FOR 50 AMP NEEDS TO BE PROTECTED BY 50 AMP BREAKER OR INSTALL #6 NEC 240.4, 110.14, 110.3 AND 310.15 2) CANNOT USE TECH SCREWS FOR CONNECTION OF EQUIPMENT GROUNDS OR GROUND BARS. USE MACHINE SCREW OR NUT AND BOLT 4) #8 GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED IN RACEWAY ON CABLE ARMOR NEC 250.64 AND 690.47 5) LABELS TO BE PER PLANS AND NEC 690 AND BE ABLE TO WITHSTAND ENVIORMENT ALREADY COMING OFF 6) CANNOT USE PLASTIC BOXES WITH METAL RACEWAY NEC 314.3 7) BOND AROUND REDUCING WASHER OR INSTALL PER DIRECTIONS 8) DERATE WIRES TO 1 1/4" EAST TO OLD SERVICE LOCATION |