Permit: T10CM02563

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/24/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/19/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOW VOLTAGE BUSHING MISSING
2) OPEN J-BOXES
3) A/C CONTACTOR TO BE IN BOX
4) STRAP ON EMT MISSING
05/02/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/10/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK PHASE 4
02/16/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/03/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/01/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PHASE 3 CEILING ELECTRICAL OKAY
2) CEILING PHASE 3 LOW VOLTAGE WIRE TO BE OFF CEILING GRID
3)PHASE 4 WALL ON EAST SIDE OKAY
01/21/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PHASE 3 WALLS IN BLDG OK
12/17/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 2 LOW VOLTAGE BOXES TO BE CLOSED ON FINAL
2) LOW VOLTAGE WIRES TO BE STRAPPED ON NORTH WALL
11/17/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* OK FINAL PHASE 1 .
CHECK EXIT LIGHTS WORKING.