Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/03/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADDRESS NOT CORRECT-PV SYSTEM TIED INTO 639/645 E. SPEEDWAY ? 2) PROVIDE WIRING SIGN ON SERVICE EQUIP. PER 610 NEC 3) WHERE IS THE 100 AMP BREAKER FOR PV AS SHOWN ON PLAN-ONE LINE ? |