Permit: T10CM02558

Parcel: 13101432D

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM02558

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/07/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
10/05/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP ON CONDENSATE DRAIN LINE
2) PROVIDE A SEALED RETURN AIR PLENIUM
3) AIR CANNOT BE RETURNED FROM ANOTHER UNIT
4) REPLACE DAMAGED BATHROOM EXHAUST FAN
5) PROVIDE MINIMUM 1/8" PER FT. SLOPE ON CONDENSATE DRAIN LINE