Permit: T10CM02557

Parcel: 128100810

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/15/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
12/14/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) NEED TO TEST HEAT SENSOR OR PROVIDE INTERLOCK BETWEEN EXHAUST FAN AND COOKING EQUIPMENT
2) CAPTURE AND CONTAINMENT OK
3) EXTEND SEWER VENT MINIMUM 2' ABOVE MAU
4) PAINT EXPOSED BLACK IRON
5) PROVIDE AIR BALANCE REPORT