Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 12/14/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO TEST HEAT SENSOR OR PROVIDE INTERLOCK BETWEEN EXHAUST FAN AND COOKING EQUIPMENT 2) CAPTURE AND CONTAINMENT OK 3) EXTEND SEWER VENT MINIMUM 2' ABOVE MAU 4) PAINT EXPOSED BLACK IRON 5) PROVIDE AIR BALANCE REPORT |