Permit: T10CM02557

Parcel: 128100810

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T10CM02557

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2010 MECHANICAL - HOODS Approved IVRS - Inspection :*
11/24/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SPRINKLER PIPE CANNOT BE WRAPPED WITH FIRE BLANKET
2) RELOCATE THE SPRINKLER PIPE OR OFFSET THE GREASE DUCT
11/19/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCT
2) SPRINKLER PIPE IS IN THE WAY OF WRAPPING WITH 2 LAYERS-OK FOR BOTH LAYERS