Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* NOTES ARE FOR BOTH ADDRESSES: 1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET 2) INSULATE SHEET METAL SLEEVE ON FAN COIL |
|
| 09/27/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES ARE FOR BOTH ADDRESSES: 1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. OK TO TERMINATE TO WITHIN 6" OF DIRT. SUPPORT COPPER DRAIN LINE EVERY 6' 2) LOW VOLTAGE WIRE MUST BE PROTECTED FROM DAMAGE 3) DISCONNECT OVERFUSED 4) SLEEPERS NEED TO BE LONGER TO SPAN MORE JOISTS. PROVIDE ROOF TOP DRAWING FOR NEW A/C TO SHOW STRUCTUAL INTEGRITY 5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF 6) ID A/C CIRCUIT BREAKERS 7) PROVIDE ACCESS INTO APT. |