Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1) PLESE HAVE PREVIOUS INSPECTION WRITE UP ON SITE |
|
| 09/27/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) LABELING TO BE PER 690.17 ON ALL DISCONNECTING MEANS 2) WEEB LUG NOT INSTALLED PER INSTRUCTIONS 3) PLEASE PROVIDE GROUND LUG DETAIL FOR MODULES TO VERIFY STAR WASHER POSITION FOR EFFECTIVE GROUND FAULT PATH |