Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 10/20/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT TERMINATE T & P DRAINS ON WATER HEATER TO THE ROOF. T & P MUST SLOPE DOWNHILL TO DAYLIGHT OR USE THE ALTERNATE METHOD 2) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR 3) BAROMETRIC DAMPER MUST BE ACCESSIBLE 4) SILICON CAULKING NOT APPROVED FOR PVC GLUE. PROVIDE PURPLE PRIMER PRIOR TO GLUING JOINTS 5) PROVIDE A ROOF JACK FOR EXHAUST AND DRAIN LINE ON ROOF. PAINT EXPOSED PVC WITH LATEX PAINT |
|
| 10/13/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE RESCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME |