Permit: T10CM02536

Parcel: 12703012B


Addresses:

5532 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/11/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/06/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTEND SEWER VENTS MINIMUM 2' ABOVE ANY AIR INTAKE
2) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX
3) PERMANENTLY I.D. ALL EQUIPMENT ON ROOF
4) EXTEND WATER HEATER VENT 3' ABOVE WALL
5) PLANS CALL FOR A/C 6 + 9 TO HAVE DUCT SMOKE DETECTORS
6) 6 EXHAUST FANS ARE DISCHARGING TO CLOSE TO WALL OF ROOF
7) THERE IS NO OUTSIDE AIR SCHEDULE ON PLANS
8) NEED CAPTURE AND CONTAINMENT TEST & HEAT SENSOR TEST