Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/27/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL TAPE FROM FLUE PIPE 2) PROVIDE A MINIMUM 3 SCREWS AT ALL SINGLE WALL FLUE PIPE JOINTS 3) ALL PVC PIPE JOINTS TO HAVE PRIMER, PRIMER IS TO BE PURPLE IN COLOR PER U.P.C. 4) CONDENSATE NOT PROPERLY TERMINATED 5) ALL FOAM PIPE INSULATION EXPOSED TO DAYLIGHT IS TO BE COATED TO PROTECT FROM U.V. 6) T-STAT WIRE EXPOSED TO EXTERIOR IS TO BE PROTECTED BY CONDUIT OR OTHER MEANS |